Power for the grid
we are building next.

215 kWPer power module
99.0%Peak efficiency
1500 VDC window
70 msEMS response
3440 kWPer skid

One power module.
Every system.

A liquid-cooled drawer, and the skid that carries sixteen of them. Scroll to take each one apart.

CCE-PCS-150k · 750 × 825 × 230 mm · ≤ 98 kg

Power conversion system

CCE-PCS-150k

150 kW, grid-forming, liquid-cooled. Sealed in a plug-in drawer.

Everything connects at the front. DC in and AC out on plug-in connectors, with communications and status beside them. A drawer is replaced without rewiring.

Open it, and it opens up. A sealed Type 3R enclosure around three clean layers: the DC link, the power stage and the lid.

A liquid-cooled power stage. Three-level NPC phase legs share one cold plate. No dust filters, no outside air in the electronics.1

The DC link, filtered. Film capacitors, common-mode cores and the precharge board sit on their own bracket in the lower bay.1

One chassis, two ratings. The same 750 × 825 × 230 mm drawer carries 150 kW at 480 V, or 215 kW at 690 V as the CCE-PCS-215k.

CCE-MVSkid-3440 · 3440 kW · 16 × CCE-PCS-215k

Medium-voltage skid

CCE-MVSkid-3440

Sixteen modules, liquid cooling and the MV transformer. One lift.

Sealed to IP55. Each cabinet carries its own dry cooler on the roof, serving a closed liquid loop.

Everything inside, installed at the factory. Modules, cooling, controls and transformer arrive as one tested system.

Sixteen CCE-PCS-215k. Four drawers per cabinet. Every string is controlled on its own, and any one slides out from the front.

Your transformer, integrated. 3440 kVA, 6–37 kV to 0.69 kV, oil-immersed or dry-type, specified by you.2

Set on piers. Bolted down. Energised.

CCE-BMS · 3-level · BAU / BMU / CMU

Battery management system

CCE-BMS

Three levels, from every cell to the whole array.

Level 1, the CMU. At the battery module, on a daisy chain. This is where the system meets the cells.

Level 2, the BMU. It gathers its CMUs and works with the relay, the breaker and the Hall sensor.

Level 3, the BAU. The array controller: CAN down to the BMUs, CAN and RS485 to the PCS, Ethernet to the EMS.

SOC within 2.5%, SOH within 4%. Fail-safe shutdown, and security to IEC 62443 built into the controller.

Specifications

Three products.
One platform.

The same power module, chassis, cooling circuit and control firmware, from a single drawer to a 3440 kW skid.

All datasheets

CCE-PCS-150k

150kW480 V power module

CCE-PCS-215k

215kW690 V power module

CCE-MVSkid-3440

3440kW16 × CCE-PCS-215k

Electrical

AC output

480 V, 3P3W690 V, 3P3W690 V · 6–37 kV MV

DC operating range

800–1500 V1000–1500 V1000–1500 V

Efficiency

Datasheet99.0 % max.99.02 % PCS

Operating modes

PQ · VF · VSG · GFM, with black start

Mechanical

Dimensions (W × D × H)

750 × 825 × 230 mm6058 × 2438 × 2896 mm3

Weight

≤ 98 kg≤ 15 t

Enclosure

Type 3R · C4Type 3R / IP65 · C4IP55 / Type 3R

Cooling

Liquid, sealed loop

Environment and compliance

Operating temperature

−30 to +60 °C

Protocols

Modbus TCP/RTU, CANModbus, IEC 104, IEC 61850Modbus, IEC 104, IEC 61850

Standards

On requestUL 1741 SB, IEEE 1547, IEEE 519UL 1741 SB, IEEE 1547, IEC 62933
  1. Enclosure, partition, chassis, inductor housing and fasteners of the CCE-PCS-150k are shown from production CAD. Power electronics, magnetics, fans and connectors are drawn at their CAD mounting points for illustration.
  2. The MV transformer is customer-specified and shown as a typical oil-immersed unit.
  3. Datasheet dimensions, 20-ft skid. The skid shown is a production CAD arrangement of about 10.0 × 3.2 × 3.1 m.

Manufacturing

Built in the United States.
Tested before it ships.

01

Domestic content

Integrated under one roof, with a traceable bill of materials.

02

Full-power testing

Every skid is wired, filled and commissioned at the factory. The report ships with the serial number.

03

Engineering on the floor

Design and production share one building.

Full-power test bay

Every unit runs at rated power before it leaves the building.

Final assembly and test · United States

Contact

Send us the single-line diagram.

Houston, Texas · Response within one business day